How does a fixed CO2 flooding fire-extinguishing system work?

A fixed CO2 system floods a sealed, evacuated space such as an engine room with carbon dioxide, cutting the oxygen until the fire can no longer burn.

Updated 2026-11-09

Short answer

A fixed CO2 system puts out a fire in a closed space by flooding it with enough carbon dioxide to cut the oxygen below the level combustion needs. It protects spaces such as engine rooms, cargo pump rooms and cargo holds. The space must be evacuated and sealed first, because CO2 at extinguishing concentration kills people within minutes.

In detail

The gas is kept in banks of high-pressure cylinders, or in a refrigerated low-pressure tank, in a CO2 room outside the protected spaces. The FSS Code sets the quantity. For machinery spaces the system must hold enough gas for the largest space: the larger of 40 percent of its gross volume, leaving out the upper casing, or 35 percent including the casing. In machinery spaces, 85 percent of that gas must be able to reach the space within two minutes, so the fire is smothered before it can spread. For cargo holds the amount is 30 percent of the gross volume of the largest hold.

Release is manual and takes more than one action on purpose. The pre-discharge alarm in the protected space must start automatically, and on most systems opening the release cabinet door sets it off. In spaces where people work or have access, the alarm must sound for long enough to get everyone out, and never less than 20 seconds, before any gas is released. The FSS Code then requires two separate controls. One opens the valve to the chosen space and the other releases gas from the containers, and they can only be operated in that order.

Using the system is the master's decision, taken when the fire cannot be fought any other way. The usual sequence is:

  • Muster the crew and account for every person. Confirm that nobody is left in the space.
  • Stop fuel and lubricating oil pumps, close the quick-closing valves and stop machinery.
  • Stop the ventilation and close all dampers, skylights, doors and other openings.
  • Release the number of cylinders shown for that space on the release instructions.

After release, keep the space closed. Watch boundary temperatures from outside, often for many hours. Opening up too early lets air in to a hot fire, which can reignite, and there is normally only one full charge of gas on board. When the boundaries have cooled, a team in breathing apparatus makes the first entry through a small opening. The space is then ventilated and its atmosphere tested before anyone goes in without breathing apparatus.

The crew inspect the CO2 room, release controls and alarms at set intervals under the ship's maintenance plan, which follows IMO guidance in MSC.1/Circ.1432 and MSC.1/Circ.1318/Rev.1. The contents of the cylinders are checked by weighing or a liquid level gauge at the intervals that guidance sets, usually by a specialist service firm, and any cylinder holding less than 90 percent of its nominal charge is refilled. Accidental releases have killed people, so keep the CO2 room locked, treat it with the care of an enclosed space and investigate any CO2 alarm at once.

Related Terms

Continue Reading

More Questions in Shipboard Operations

What should be checked during engine-room watchkeeping rounds?

An engine-room round compares readings, sounds and smells with normal values for the current load, logs real figures and spots trends before alarms do.

What is a toolbox talk and when is it done?

A toolbox talk is a short safety briefing at the job site before work starts, held before higher-risk work and repeated whenever the job or conditions change.

What must be checked before enclosed space entry?

The core precautions before entering an enclosed space — atmosphere testing, permit, ventilation, standby and communications — because these spaces still kill seafarers.

What are the key steps in a safe bunkering operation?

Safe bunkering means an agreed plan and checklist, deck prepared against spills, close watch at topping off, a MARPOL sample and checked delivery figures.